1. General introduction

YTA610 temperature transmitter is a basic field mounted type with basic diagnosis function, accepts single or dual signal of Thermocouples, RTD, ohms or DC mill volts inputs and converts it to a 4 to 20 mA DC or Field bus signal for transmission. It supports HART and Foundation field bus communication protocols. HART types are certified as complying with SIL2 for safety requirement.

2. Sensors inputs, measure range and accuracy

Sensor Type

Standard

Measure range

Minimum

span

A/D Accuracy

D/A Accuracy

T/C

B

IEC60584

100 to 300

300 to 1820

212 to 572

572 to 3308

25℃

(45℉)

±3.0

±0.77

±5.4

±1.39

±0.03% of span

E

-200 to -50

-50 to 1000

-328 to -58

-58 to 1832

±0.4

±0.2

±0.72

±0.36

J

-200 to -50

-50 to 1200

-328 to -58

-58 to 2192

±0.35

±0.25

±0.63

±0.45

K

-200 to -50

-50 to 1372

-328 to -58

-58 to 2502

±0.5

±0.3

±0.9

±0.54

N

-200 to -50

-50 to 1300

-328 to -58

-58 to 2372

±0.5

±0.4

±0.9

±0.72

R

-50 to 0

0 to 600

600 to 1768

-58 to 32

32 to 1112

1112 to 3214

±1.0

±0.7

±0.5

±1.8

±1.26

±0.9

S

-50 to 0

0 to 1768

-58 to 32

32 to 3214

±1.0

±0.6

±1.8

±1.08

T

-200 to 50

-50 to 400

-328 to -58

-58 to 752

±0.35

±0.2

±0.63

±0.36

C

0 to 2000

2000 to 2300

32 to 3632

3632 to 4172

±0.7

±1.0

±1.26

±1.8

W3

ASTM E988

0 to 400

400 to 1400

1400 to 2000

2000 to 2300

32 to 752

750 to 2552

2552 to 3632

3632 to 4172

±0.9

±0.6

±0.7

±1.0

±1.62

±1.08

±1.26

±1.8

L

DIN43710

-200 to -50

-50 to 900

-328 to -58

-58 to 1652

±0.35

±0.3

±0.63

±0.54

U

-200 to 600

-328 to 1112

±0.35

±0.63

RTD

PT100

IEC60751

-200 to 850

-328 to 1562

10℃

(18℉)

±0.14

±0.25

PT200

-200 to 850

-328 to 1562

±0.25

±0.45

PT500

-200 to 850

-328 to 1562

±0.18

±0.32

PT1000

-200 to 300

-328 to 572

±0.18

±0.32

JPT100

-200 to 500

-328 to 932

±0.16

±0.29

CU10

SAMA

RC21-4

-70 to 150

-94 to 302

±1.3

±2.34

Ni120

-70 to 320

-94 to 608

±0.14

±0.25

mV

-10 to 120 mV

3 mV

±0.015 mV

ohm

0 to 2000 Ω

20 Ω

±0.45 Ω

3. Model and suffix codes

Main Code

Suffix Codes

Description

YTA610








Temperature transmitter

Output Signal

-J







4 to 20mA DC with   digital communication HART 7 protocol

-F







Digital communication   (FOUNDATION Fieldbus protocol)


A






Always A

Sensor Input



1





Single



2





Double

Housing code




A




Aluminum




C




Stainless

Electrical connection





0



G1/2 female





2



1/2 NPT female





4



M20 female

Integral indicator






D


Digital indicator with local operating switch






N


None

Mounting bracket







B

SUS304 stainless steel   2-inch horizontal pipe mounting bracket







D

SUS304 stainless steel   2-inch vertical pipe mounting bracket







J

SUS316 stainless steel   2-inch horizontal pipe mounting bracket







K

SUS316 stainless steel   2-inch vertical pipe mounting bracket







N

None

Optional codes

/Optional codes